NEMA electrical motor starters refer to a standardized rating system for the
electrical performance of the most common style of American-built motor
starters.
NEMA starters are rated by size:
00, 0, 1, 2, 3, 4, 5, 6 and 7.
To select a NEMA starter only horsepower and voltage are needed. NEMA starters
have interchangeable heater elements and makes NEMA starters attractive in
projects where the motor specification is not known until the start-up date.
|
| Maximum Horsepower (hp) |
| NEMA Size |
NEMA Continuous Amp Rating
(Amp) |
Full Voltage Starting |
Part Winding Starting |
Wye Delta Starting |
| 200V |
230V |
460V 575V |
200V |
230V |
460V 575V |
200V |
230V |
460V 575V |
| 00 |
9 |
1 1/2 |
1 1/2 |
2 |
|
|
|
|
|
|
| 0 |
18 |
3 |
3 |
5 |
|
|
|
|
|
|
| 1 |
27 |
7.5 |
7.5 |
10 |
10 |
10 |
15 |
10 |
10 |
15 |
| 2 |
45 |
10 |
15 |
25 |
20 |
25 |
40 |
20 |
25 |
40 |
| 3 |
90 |
25 |
30 |
50 |
40 |
50 |
75 |
40 |
50 |
75 |
| 4 |
135 |
40 |
50 |
100 |
75 |
75 |
150 |
60 |
75 |
150 |
| 5 |
270 |
75 |
100 |
200 |
150 |
150 |
350 |
150 |
150 |
300 |
| 6 |
540 |
150 |
200 |
400 |
|
300 |
600 |
300 |
350 |
700 |
| 7 |
810 |
|
300 |
600 |
|
450 |
900 |
500 |
500 |
1,000 |
|
|
TYPE 4 ENCLOSURES
Type 4 enclosures are intended for indoor or outdoor use primarily to provide a
degree of protection against windblown dust and rain, splashing water, and
hose-directed water; and to be undamaged by the formation of ice on the
enclosure. They are not intended to provide protection against conditions such
as internal condensation or internal icing.
TYPE 4X ENCLOSURES
Type 4X enclosures are intended for indoor or outdoor use primarily to provide a
degree of protection against corrosion, windblown dust and rain, splashing
water, and hose-directed water; and to be undamaged by the formation of ice on
the enclosure. they are not intended to provide protection against conditions
such as internal condensation or internal icing.
TYPE 12 ENCLOSURES
Type 12 enclosures are intended for indoor use primarily to provide a degree of
protection against circulating dust, falling dirt, and dripping non-corrosive
liquids. They are not intended to provide protection against such conditions as
internal condensation. COMPARISON BETWEEN NEMA ENCLOSURE TYPE NUMBERS AND IEC
ENCLOSURE CLASSIFICATION DESIGNATIONS
Electrical panels,
code requirements, switch gear, transformers, lighting ballasts, most
common Wiring
Diagram No.1 for NEMA Receptacle Configurations

The National Electrical Code,
GFI
receptacles, grounding rods and cold water pipe grounding.
Repairs and replacements of under cabinet lights, front
lawn post lights and area flood lights such as high pressure
sodium and medal halide. Electrical safety inspections main
lug panel, cadmium connectors, MC wire, SER cable, SEU
cable, twist-lock
Philadelphia,
PA, receptacle charts, wiring diagrams, GFI, receptacles,
grounding rods, Commercial, Industrial, cadmium connectors,
MC wire, SER cable, SEU cable, twist-lock, grounding, We are
installers. The National Electrical Manufacturers
Association, NEMA.
|